D-500L Firmware V-5.8
K35D03-EN - 79 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
SMS on Engine
Run/Stop
-
0
1
0
This parameter controls SMS sending
when the engine runs or stops. No
warnings generated.
0: no SMS on engine run/stop
1: SMS sent on engine run/stop
E-mail on Engine
Run/Stop
-
0
1
0
This parameter controls e-mail sending
when the engine runs or stops. No
warnings generated.
0: no e-mail on engine run/stop
1: e-mail sent on engine run/stop
Fuel Counter Type
-
0
1
0
This parameter determines the purpose
of fuel pulses
0: Fuel filling pulses, increment fuel
counter
1: Fuel consumption pulses, display
consumption.
Dual Genset Equal Aging
Enabled
-
0
1
0
0: Equal aging not enabled
1: Equal aging enabled
CT Secondary Rating
-
0
1
0
0: xxx/5A
1: xxx/1A
Automatic Topology
Detection
-
0
1
0
If this parameter is enabled, when the
engine runs, the controller will detect
the connection topology automatically
and will select alarm levels accordingly.
0: auto detect not enabled
1: auto detect enabled
Maintenance Done
Warning Enable
-
0
1
0
If enabled, the unit will generate a non-
visual warning when maintenance
counters are reset. In consequence,
SMS and e-mails will be sent, the
warning will be visible on the central
monitoring system.
0: maintenance warning disabled
1: maintenance warning enabled
Stop Status Screens
-
0
1
0
0: Enable status screens
1: Disable status screens
Time Zone
min
-720
+720
0
This parameter adjusts the time zone of
the controller, in order to allow internal
real time clock to be synchronized to
the UTC time.
GSM Location
Information
-
0
1
0
0: no location information from GSM
1: location information read from GSM
system.
Disable STOP at
Loaddump
-
0
1
0
0: When Loaddump alarm occurs,
genset contactor opens and genset
runs until the end of the cooldown
period.
1: When Loaddump alarm occurs,
genset contactor opens but the genset
continues running without timeout.
16.1. CONTROLLER CONFIGURATION GROUP (continued)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Datakom D Series and is the answer not in the manual?

Datakom D Series Specifications

General IconGeneral
BrandDatakom
ModelD Series
CategoryController
LanguageEnglish

Related product manuals