D-500L Firmware V-5.8
K35D03-EN - 86 -
If a genset MCB feedback input is
defined and if the genset MCB fails to
change position before the expiration of
this timer, then a fault condition occurs.
Genset Phase Order
Check Enable
0: genset phase order checking
disabled
1: if genset phase order is faulty, then a
genset phase order fail loaddump alarm
is given.
When a genset closes to the Busbar, if
the mater genset controller does detect
the Busbar voltage at the expiration of
this period, a “BUSBAR FAIL” fault
condition will occur.
This is the delay after all generators
close to the busbar and before the
master genset controller acknowledges
“Busbar ready” signal.
Multi Load Subtract
Power Level
When the genset active power goes
over this limit, the controller will start
subtracting load as described in chapter
Five Step Load Management.
Multi Load Add Power
Level
When the genset active power goes
below this limit, the controller will start
adding load as described in chapter
Five Step Load Management.
Multi Load Subtract Start
Delay
If the load stays over the Multi Load
Subtract Power Level parameter
during this timer, then 1 step of load is
subtracted.
Multi Load Subtract Wait
Delay
This is the minimum period between
two load subtract operations.
Multi Load Add Start
Delay
If the load stays below the Multi Load
Add Power Level parameter during this
timer, then 1 step of load is added.
Multi Load Add Wait
Delay
This is the minimum period between
two load add operations.
Excess power Warning
Limit
If the genset active power goes above
this limit then the controller will give an
Excess Power Warning.
16.2. ELECTRICAL PARAMETERS GROUP (continued)