5. Check the following parameters:
Tab.15
Code Description Adjustment required
NP006 Cascade Type Traditional
NP009 CascInterStageTime 4
NP011 CascadeTypeAlgo Temperature
6. Press the key.
7. Select Installation Setup.
8. Configure the parameters for the following components:
Tab.16
Component Access Parameter Code Adjustment required
Recirculating pump AUX Functionality of the zone CP024 Time Program
Stratified tank Analogue input > Adv.
Parameters
Sets the general configuration of
the sensor input 1
EP036 DHW tank top
DHW Functionality of the zone CP022 DHW Layered
6 Connecting diagrams and configuration