EasyManua.ls Logo

Deger MLD Control - Connection; Block Diagram

Deger MLD Control
35 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
01/10/2021 ASSEMBLY INSTRUCTIONS MLD Control EC-6 with CCB III Page 24
6 Connection
6.1 Block diagram
DANGER!
Only trained and qualified personnel may connect the EC-6 to the CCB. The EC-6 should only be
connected to the CCB when no voltage
is present.
DANGER!
The external voltage supply must meet the regional regulations. The EC-6 must be able to be
disconnected from the supply voltage by a 10 A-B or 6 A-C circuit breaker; the CCB by a 3 A-B
circuit breaker. The circuit breaker must be fully accessible.
3 x 0.5 mm²
or
3 x 1 mm²
4 x 0.5 mm²
2 x 0.5 mm²
3 x 1 mm²
2 x 1 mm²
This diagram is an example. The wire cross section has to be dimensioned according to the cable length and
to the local requirements.
Snow sensor
(optional)
MLD sensor
for AZ
EL
motor
MLD sensor
for EL
AZ
motor
Anemometer
Wind monitor
EC-6
Evaluation unit
Wind monitor
CCB
Power
AC 100-240 V
Additional EC-6
Additional EC-6
Additional EC-6
Additional EC-6
4 x 0.5 mm² or
8 x 0.5 mm²