01/10/2021 ASSEMBLY INSTRUCTIONS MLD Control EC-6 with CCB III Page 14
4 Wind Monitor
4.1 Wind monitor
The wind alarm becomes activated when the wind speed exceeds continuously the default setting of 12 m/s.
The alarm will stop when the wind speed is continuously slower than the default setting of 10 m/s for a
duration of approximately 10 minutes. If the wind speed exceeds 10 m/s within these 10 minutes, the time
will start over for another 10 minutes.
Speed [ m/s ]
Relay is deactivated
Wind alarm Wind alarm stops
12m/s
10m/s
1s 10 min
Time [ ]
Relay is reactivated
The alarm can be cancelled early by unlocking the power reset
4.1.1 Pin assignment
Note: If you have our old wind monitor with our new anemometer, then please refer to page 19 & 25 for
installation
Terminal
designation
Function
AC Power
Supply
Supply voltage
- AC 100 to 240 V
- 1.1 A
Red and Blue Wires
22
Switch contact for wind alarm, potential-free
Green Wire
Connection for CCB
+
Switch contact for wind alarm, potential-free
Red Wire
Connection for CCB
Evaluation unit
CCB
Cable length 20 m