Figure 7.8 Example of using a current output for voltage regulation
+
-
GOV/AVR
R
Typical values for the resistor is 2.5 kΩ, while the potentiometer is 5 kΩ.
INFO
You do not have to use a current output for voltage regulation. You can configure and connect an available voltage output
directly instead. However, if the controller loses power, the output is an open circuit with infinite resistance.
7.5 Power management wiring
7.5.1 Heavy consumer
MORE INFORMATION
See Power management, Heavy consumer management, Heavy consumer function in the Designer's handbook for
information about setting the parameters for these configurations.