See Wiring the controller hardware modules, Input/output module IOM3.4 for examples of how to wire the specific
terminal types.
5.3 EIM3.1 terminal connections and default wiring
5.3.1 EIM3.1 terminal connections
This information only applies to the GENSET and EMERGENCY genset controllers. There is no default configuration for EIM 3.1 for
the other controller types.
Terminal Name Type Default
F/G F/G Ground Frame ground*
1 + 12 or 24 V DC (nominal)**
Power supply*
2 - 0 V DC
3
Normally
open
Relay output (30 V DC and 6 A)
... > Crank
4 Common
5
Normally
open
Configurable
6 Common
7
Normally
open
Configurable
8 Common
9
Normally
open
Relay output with wire break detection (30 V DC and 6 A) ... > Stop coil
10 Common
11
Digital input (OFF: 0 to 2 V DC, ON: 8 to 36 V DC,
Impedance: 4.7 kΩ)
... > Start enable
12 Configurable
13 Configurable
14 Configurable
15 Common Digital input
16
MPU input (Voltage: 2 to 70 V AC peak, Frequency: 2 to
20,000 Hz)
Magnetic pickup
17 Common MPU or W input
18
W input (Voltage: 8 to 36 V AC, Frequency: 2 to 20,000
Hz)
Generator tacho or
NPN/PNP sensor
19 Analogue current or resistance measurement input (RMI)
(Current input: 0 to 20 mA, or 4 to 20 mA;
Pt100/1000:-40 to 250 ºC;
Resistance measurement: 0 to 2.5 kΩ;
Digital input (dry contact with cable supervision): maximum
330 Ω for ON detection;
Minimum current rating for connected relays: 2.5 mA)
Configurable
20 Configurable
21 Configurable
22 Common Analogue input
*Note: You cannot change this.
INSTALLATION INSTRUCTIONS 4189340909I UK Page 51 of 144