1 Normally open
Relay output (250 V AC or 30 V DC, and
6 A)
... > GOV increase (Configurable)*
2 Common
3 Normally open
... > GOV decrease
(Configurable)*
4 Common
5 Normally open
Configurable
6 Common
7 Normally open
Configurable
8 Common
9 Active (P) load
Voltage output: -5 to 5 V DC,
Impedance: 23.5 kΩ
Load sharing for future use to
perform analogue load sharing
10 Common
11
Reactive (Q)
var
12 Output Analogue current or voltage output
(Current: 0 to 20 mA, 4 to 20 mA, or -20
to 20 mA;
Voltage (DC): 0 to 10 V, -10 to 10 V, 0 to
5 V, 0 to 3 V, -3 to 3 V, 0 to 1 V)
Configurable
13 Common
14 PWM output
Frequency: 500 Hz ±50 Hz, Resolution:
43,200 levels, Voltage: 0.05 to 6.85 V
Pulse width modulation (PWM)
output
15 Common
16 Output Analogue current or voltage output
(Current: 0 to 20 mA, 4 to 20 mA, or -20
to 20 mA;
Voltage (DC): 0 to 10 V, -10 to 10 V, 0 to
5 V, 0 to 3 V, -3 to 3 V, 0 to 1 V)
Configurable
17 Common
18 Input
Analogue current or voltage input
(Current: 0 to 20 mA, or 4 to 20 mA;
Voltage (DC): -10 to 10 V, 0 to 10 V)
Configurable
19 Common
20 Input
Configurable
21 Common
*Note: The default terminal connections use relay connections for governor control. However, the governor can also be controlled
using an analogue output (terminals 12 and 13, and terminals 16 and 17), or pulse width modulation (terminals 14 and 15). You can
read more about these terminals in the chapter on Wiring the controller hardware modules, and in the Designer's handbook.
INSTALLATION INSTRUCTIONS 4189340909I UK Page 54 of 144