Normally open
Relay output with wire break detection (30 V DC and 6 A)
10 Common
11 Bi-directional input
Digital input (OFF: 0 to 2 V DC, ON: 8 to 36 V DC, Impedance: 4.7 kΩ)
12 Bi-directional input
13 Bi-directional input
14 Bi-directional input
15 COM Common Common for digital input terminals 11 to 14
16
MPU input with wire btreak detection (Voltage: 2 to 70 V AC peak, Frequency: 2 to
20,000 Hz)
17 COM Common MPU or W input
18 W W input (Voltage: 8 to 36 V AC, Frequency: 2 to 20,000 Hz)
19 Analogue current or resistance measurement input (RMI)
(Current input: 0 to 20 mA, or 4 to 20 mA;
Pt100/1000: -40 to 250 ºC;
Resistance measurements: 0 to 2.5 kΩ;
Digital inputs (dry contact with cable supervision): maximum 330 Ω for ON detection;
Minimum current rating for connected relays: 2.5 mA)
20
21
22 COM Common Analogue input common
*Note: Class societies require an independent power supply for the EIM. The EIM must therefore not be connected to the same
power supply source as the PSM.
6.6.2 Frame ground wiring
Connect the frame ground terminal to ground/earth.
INFO
The frame ground terminal must be connected to the cabinet. The controller rack must also be connected to the cabinet, to
create a protective earth.
CAUTION
The frame ground is connected to the power supply terminals through transient voltage suppression diodes (commonly
known as transorbs). In order to protect the frame ground and power supply, no more than 36 V is allowed between the
frame ground and the power supply terminals.
6.6.3 Power supply wiring
Connect the power supply (+) to the 12 or 24 V DC power supply.
Connect the power supply (-) to the 0 V DC power supply.
INSTALLATION INSTRUCTIONS 4189340909I UK Page 76 of 144