5. Default wiring for the optional modules
5.1 IOM3.1 terminal connections and default wiring
5.1.1 IOM3.1 terminal connections
GENSET, SHAFT generator, SHORE connection and BUS TIE breaker controllers
Terminal Name Type Default
1 Normally open
Relay output (250 V AC or 30 V DC, and 6 A)
... > Control > [Close]
2 Common
3
Normally
closed
4 Normally open
... > Control > [Open]
5 Common
6
Normally
closed
7 Normally open
Configurable
8 Common
9
Normally
closed
10 Normally open
Configurable
11 Common
12
Normally
closed
13
Digital input (OFF: 0 to 2 V DC, ON: 8 to 36 V DC,
Impedance: 4.7 kΩ)
... > Feedback >
[Open]
14
... > Feedback >
[Closed]
15 Configurable
16 Configurable
17 Configurable
18 Configurable
19 Configurable
20 Configurable
21 Configurable
22 ... > PMS control
23 Common Digital input
INSTALLATION INSTRUCTIONS 4189340909I UK Page 43 of 144