Table 5.1 Controller specific breaker names
Controller
[Close] GB close SGB close SCB close BTB close
[Open] GB open SGB open SCB open BTB open
[Closed] GB closed SGB closed SCB closed BTB closed
EMERGENCY genset controller
Terminal
Name Type Default
1
Normally
open
Relay output (250 V AC or 30 V DC, and 6 A)
... > Control > GB close2 Common
3
Normally
closed
4
Normally
open
... > Control > GB open5 Common
6
Normally
closed
7
Normally
open
... > Control > TB close8 Common
9
Normally
closed
10
Normally
open
... > Control > TB open
11 Common
12
Normally
closed
13
Digital input (OFF: 0 to 2 V DC, ON: 8 to 36 V DC,
Impedance: 4.7 kΩ)
... > Feedback > GB open
14 ... > Feedback > GB closed
15 ... > Feedback > TB open
16 ... > Feedback > TB closed
17 Configurable
18 Configurable
19 Configurable
20 Configurable
21 Configurable
22 ... > PMS control
23 Common Digital input
INSTALLATION INSTRUCTIONS 4189340909I UK Page 44 of 144