EasyManua.ls Logo

Deif PPM 300 - 6 Wiring the Controller Hardware Modules; Introduction; Power Supply Module PSM3.1; PSM3.1 Terminal Overview

Deif PPM 300
144 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6. Wiring the controller hardware modules
6.1 Introduction
6.1.1 Introduction
This chapter describes the wiring for each of the controller hardware modules in detail. Each terminal's wiring is described, with
examples. Wiring the CAN bus communication to a genset is also included in this chapter. However, wiring the system
communication (including the connection to the display unit) is described in another chapter.
The Data sheet contains all the technical specifications for all the terminals.
The default wiring for the controller type is described in the chapter Default wiring for controller types.
DANGER!
You must only use the terminal blocks supplied with the controller and display unit. Do not use substitutes.
6.2 Power supply module PSM3.1
6.2.1 PSM3.1 terminal overview
Terminal
Symbol Name Type
F/G F/G Ground
1
+
-
+ 12 or 24 V DC (nominal)
2 - 0 V DC
3 Normally open
Relay output (30 V DC and 1 A)
4 Common
5 Normally open
6 Common
7 Normally open
8 Common
Table 6.1 PSM3.1 Internal communication connections
Connection Symbol Name Type
Bottom of rack, front
Future use: Internal communication input connection to connect
several extension racks.
Internal communication input
Bottom of rack, back
Future use: Internal communication output connection to
connect several extension racks.
Internal communication output
INFO
Internal communication connections must only be used for internal communication.
6.2.2 Frame ground wiring
Connect the frame ground terminal to ground/earth.
INSTALLATION INSTRUCTIONS 4189340909I UK Page 59 of 144