EasyManua.ls Logo

Deif PPM 300 - Governor and AVR Module GAM3.1; GAM3.1 Terminal Overview

Deif PPM 300
144 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 6.40 Connection of a dry contact with cable supervision, and short circuit detection
COM
R1
R2
Requirements:
The maximum resistance for the circuit and resistor (R1) is 330 Ω.
The resistance of R2 must be less than R1.
R1 must be connected to the switch, and not to the controller terminals.
6.7 Governor and AVR module GAM3.1
6.7.1 GAM3.1 terminal overview
Terminal
Symbol Name Type
1 Normally open
Relay output (250 V AC and 8 A, or 30 V DC and 5 A)
2 Common
3 Normally open
4 Common
5 Normally open
6 Common
7 Normally open
8 Common
9
P
Active (P) load
Load sharing for future use to perform analogue load sharing. (Voltage output: -5 to 5 V DC,
Impedance: 23.5 kΩ)
10 COM Common
11
Q
Reactive (Q)
var
12 Output
Analogue current or voltage output
(Current: 0 to 20 mA, 4 to 20 mA, or -20 to 20 mA;
Voltage (DC): 0 to 10 V, -10 to 10 V, 0 to 5 V, 0 to 3 V, -3 to 3 V, or 0 to 1 V)
13 Common
14 PWM output
Pulse width modulation (PWM) output
(Frequency: 500 Hz ±50 Hz, Resolution: 43,200 levels, Voltage: 0.05 to 6.85 V)
15 Common
16 Output
Analogue current or voltage output
(Current: 0 to 20 mA, 4 to 20 mA, or -20 to 20 mA;
Voltage (DC): 0 to 10 V, -10 to 10 V, 0 to 5 V, 0 to 3 V, -3 to 3 V, or 0 to 1 V)
17 Common
INSTALLATION INSTRUCTIONS 4189340909I UK Page 91 of 144

Table of Contents

Other manuals for Deif PPM 300

Related product manuals