CAUTION
Protect the display unit terminals from static discharge during installation. Protecting the terminals is very important while
the frame ground is not connected.
Ventilation requirements and spacing
For proper ventilation, the display unit must be mounted with its back vertical, and its long axis horizontal. The writing on the front of
the display unit must be horizontal. Inside the cabinet, there must be a minimum of 20 mm (0.8 in) free space above, below and
behind the display unit.
Cable requirements and spacing
Figure 3.3
Example of the minimum space to the right and below the display unit for Ethernet and power supply cables (plug =
40 mm, plus cable bend radius = 40 mm)
For the Ethernet cables, the bends must not be tighter than the minimum bend radius specified by the cable manufacturers. You
must therefore ensure that there is enough space to the right of the display unit (as seen from the front) for the Ethernet cables.
INFO
DEIF recommends that you always follow the cable manufacturer's bend radius requirements. As a guideline, Ethernet
cables may require a minimum bend radius of around 40 mm (1.6 in).