Storage conguration 4x 3.5-inch cable
drive
8x 3.5-inch drive 16x 2.5-inch drive
Processor number TDP (W) Core count Ambient support = 35°C
Intel Xeon Bronze
3106
85 8 Yes Yes Yes
Intel Xeon Bronze
3104
85 6 Yes Yes Yes
Intel Xeon Silver 4112 85 4 Yes Yes Yes
Particulate and gaseous contamination specications
The following table denes the limitations that help avoid any equipment damage or failure from particulate and gaseous contamination. If
the levels of particulate or gaseous pollution exceed the specied limitations and result in equipment damage or failure, you may need to
rectify the environmental conditions. Remediation of environmental conditions is the responsibility of the customer.
Table 27. Particulate contamination specications
Particulate
contamination
Specications
Air ltration Data center air ltration denes, ISO Class 8 per ISO 14644-1 with a 95% upper condence limit.
NOTE: The ISO Class 8 condition applies to data center environments only. This air ltration
requirement does not apply to IT equipment designed to be used outside a data center, in
environments such as an oce or factory oor.
NOTE: Air entering the data center must have MERV11 or MERV13 ltration.
Conductive dust Air must be free of conductive dust, zinc whiskers, or other conductive particles.
NOTE: This condition applies to data center and nondata center environments.
Corrosive dust
• Air must be free of corrosive dust.
• Residual dust present in the air must have a deliquescent point less than 60% relative humidity.
NOTE: This condition applies to data center and nondata center environments.
Table 28. Gaseous contamination specications
Gaseous contamination Specications
Copper coupon corrosion rate <300 Å/month per Class G1 denes, ANSI/ISA71.04-2013.
Silver coupon corrosion rate <200 Å/month denes, ANSI/ISA71.04-2013.
NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.
36 Technical specications