CR#  Name  Description 
Att. 
Default 
the lower range is read as the upper range 
and vice versa.   
74 
Zero point tracking time for 
CH2 
Range: 5–500 
Unit: 100 ms 
R/W 
10 
75 
Zero point tracking range for 
CH2 
Floating-point format 
Range: 0–10000; 0: disabled 
R/W 
0 
76 
77  Calibration points for CH2  Range: 2–20 
R/W 
2 
78–117  Calibrated weight for CH2 
Floating-point format 
Calibrated weight of the calibration points 
1–20 
R/W 
- 
118  Decimal place for CH1  Range: 0–4 
R/W 
1 
119  Decimal place for CH2  Range: 0–4 
R/W 
1 
120  Alarm 
0: warning 
1: alarm 
Bit0: error in the power supply 
Bit1: error in the module hardware 
Bit2: error in the driver board 
R/W 
1 
200  State register  Refer to the explanation below. 
R/W 
- 
201  Command set  Refer to the explanation below. 
W 
0 
210 
The maximum peak value for 
CH1 
Floating-point format 
Maximum peak value for CH1   
R 
- 
211  - 
212 
The maximum peak value for 
CH2 
Floating-point format 
Maximum peak value for CH2   
R 
- 
213  - 
214 
The minimum peak value for 
CH1 
Floating-point format 
Minimum peak value for CH1   
R 
- 
215  - 
216 
The minimum peak value for 
CH2 
Floating-point format 
Minimum peak value for CH2 
R 
- 
217  - 
222  The time to record for CH1  Unit: 1 ms 
Range: 1–100 (1 ms–1 s)   
Time to record the digital value for the 
channels 
R/W 
50 
223  The time to record for CH2  50 
240  The number of records for CH1 
Range: 0–500; display the current records 
R 
-