9.4  RTU Mode 
9.4.1 CANopen Mode (AS-FCOPM) 
When the function card AS-FCOPM works with an AS series PLC, it supports three kinds of RTU modes, including AS 
Remote Communication, CANopen DS301 Mode and Delta Special Driver & AS Remote Mode. Use the knob 
FORMAT 1 to turn among three RTU modes.   
A.  RTU Communication Mode Setup Knob “FORMAT 1” 
0  AS Remote Communication 
4  CANopen DS301 
Delta Special Driver & AS Remote Mode 
 
B.  Node ID Setup Knob “ID1/ID2” 
  ID1: 0 (recommended) 
  ID2: 0 (the knob is no function; set up through ISPSoft); see the table below for the knob setting 
range. 
AS Remote Communication 
1~F 
(by the number of slaves) 
Delta Special Driver & AS Remote Mode 
1~F   
(by the number of slaves) 
CANopen DS301 
1~F   
(if the knob is at 0, the setting range is set by 
HWCONFIG) 
 
C.  RTU Communication Speed Setup Knob “FORMAT 2” 
Use the knob for setting. You cannot use ISPSoft (HWCONFIG) to set up the communication mode in this 
format. 
1  2  3  4  5  6  7  8-F 
10K  20K  50K  125K  250K  500K  1000K  NA