AS Series Module Manual 
8- 26 
Step 5: enter the command for activating the weight calibration 98 into D28007.   
Step 6: put no load on the load cell (adjustment point 1) and enter 1 into D28007. 1 represents CH1 and 2 
represents CH2. 
 
 
 
Step 7: put a load on the load cell (adjustment point 2). For multi-point adjustment, repeat this step. This 
example uses a 1 kg weight.   
 
 
 
Step 8: to complete the adjustment, enter the command for deactivating the weight calibration 99 into 
D28007. 
A characteristic curve is shown below. 
Dig ita l value
Point
1000 1 000 00
1 k g
10 kg
Adju sting two p oi nts
Weig ht