Chapter  3  Analog Input Module AS04/08AD-A 
3- 41 
3.5  Troubleshooting 
3.5.1  Error Codes 
Error 
Code 
Description 
A 
 D LED 
Indicator 
ERROR LED 
Indicator 
16#1605 
Hardware failure    OFF  ON 
16#1607 
The external voltage is abnormal.  OFF  ON 
16#1608 
The factory calibration is abnormal.  OFF  ON 
16#1801 
The external voltage is abnormal.  OFF  Blinking 
16#1802 
Hardware failure  OFF 
Blinking 
16#1804 
The factory calibration is abnormal.  OFF 
Blinking 
16#1808 
The signal received by channel 1 exceeds the range of inputs 
that the hardware can receive. 
Run: blinking 
Stop: OFF 
Blinking 
16#1809 
The signal received by channel 2 exceeds the range of inputs that 
the hardware can receive. 
16#180A 
The signal received by channel 3 exceeds the range of inputs that 
the hardware can receive. 
16#180B 
The signal received by channel 4 exceeds the range of inputs that 
the hardware can receive.
 
16#180C 
The signal received by channel 5 exceeds the range of inputs that 
the hardware can receive.
 
16#180D 
The signal received by channel 6 exceeds the range of inputs that 
the hardware can receive.
 
16#180E 
The signal received by channel 7 exceeds the range of inputs that 
the hardware can receive. 
16#180F 
The signal received by channel 8 exceeds the range of inputs that 
the hardware can receive. 
- 
When power-on, the module is not detected by CPU module.  OFF 
Blinking once 
or twice and 
after 2 
seconds, it 
blinks 
repeatedly