EasyManuals Logo

Delta C2000 Series User Manual

Delta C2000 Series
936 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #357 background imageLoading...
Page #357 background image
Chapter 11 Summary of Parameter SettingsC2000
11-22
Pr. Parameter Name Setting Range Default
03-29 ACI terminal input selection
0: 4–20mA
1: 0–10V
2: 0–20mA
0
03-30
PLC analog output terminal
status
Monitor the status of PLC analog output terminals
Read
only
03-31 AFM2 output selection
0: 0–20mA output
1: 4–20mA output
0
03-32 AFM1 DC output setting level 0.00–100.00% 0.00
03-33 AFM2 DC output setting level 0.00–100.00% 0.00
03-35 AFM1 filter output time 0.00–20.00 sec. 0.01
03-36 AFM2 filter output time 0.00–20.00 sec. 0.01
03-44
Multi-function MO output by AI
level source
0: AVI
1: ACI
2: AUI
0
03-45 AI upper level -100.00–100.00% 50.00
03-46 AI lower level -100.00–100.00% 10.00
03-50 Analog input curve selection
0: Regular curve
1: Three-point curve of AVI
2: Three-point curve of ACI
3: Three-point curve of AVI & ACI
4: Three-point curve of AUI
5: Three-point curve of AVI & AUI
6: Three-point curve of ACI & AUI
7: Three-point curve of AVI & ACI & AUI
0
03-51 AVI lowest point
Pr. 03-28=0, 0.00–10.00V
Pr. 03-28=1, 0.00–20.00mA
Pr. 03-28=2, 0.00–20.00mA
0.00
0.00
4.00
03-52 AVI proportional lowest point -100.00–100.00% 0.00
03-53 AVI mid-point
Pr. 03-28=0, 0.00–10.00V
Pr. 03-28=1, 0.00–20.00mA
Pr. 03-28=2, 0.00–20.00mA
5.00
10.00
12.00
03-54 AVI proportional mid-point -100.00–100.00% 50.00
03-55 AVI highest point
Pr. 03-28=0, 0.00–10.00V
Pr. 03-28=1, 0.00–20.00mA
Pr. 03-28=2, 0.00–20.00mA
10.00
20.00
20.00
03-56 AVI proportional high point -100.00–100.00% 100.00
03-57 ACI lowest point
Pr. 03-29=0, 0.00–20.00mA
Pr. 03-29=1, 0.00–10.00V
Pr. 03-29=2, 0.00–20.00mA
4.00
0.00
0.00
03-58 ACI proportional lowest point -100.00–100.00% 0.00

Table of Contents

Other manuals for Delta C2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Series and is the answer not in the manual?

Delta C2000 Series Specifications

General IconGeneral
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Overload Capacity150% of rated current for 60 seconds
CommunicationDeviceNet
ProtectionOvervoltage, Undervoltage, Overcurrent, Overload, Overheat
Humidity5% to 95% (non-condensing)
CoolingForced air cooling
Control ModeV/F Control, Sensorless Vector Control