EasyManua.ls Logo

Delta C2000 Series - Parameters

Delta C2000 Series
936 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 17 Safe Torque Off Function C2000
17-5
17-4 Parameters
STO Alarm Latch
Default: 0
Settings 0STO Alarm Latch
1STO Alarm no Latch
Pr. 06-44=0 STO Alarm Latch: after the reason of STO Alarm is cleared, a Reset command is
needed to clear the STO Alarm.
Pr. 06-44=1 STO Alarm no Latch: after the reason of STO Alarm is cleared, the STO Alarm will
be cleared automatically.
The STL1–STL3 error are all “Alarm latch” mode (in STL1–STL3 mode, the Pr. 06-44 function is
no effective).
Multi-function Output 1 (Relay1)
Default:11
Multi-function Output 2 (Relay2)
Default:1
Multi-function Output 3 (MO1)
Default:0
Multi-function Output 4 (MO2)
Default:66
Settings 66: SO N.O. output
68: SO N.C. output
Settings Functions Descriptions
66 SO Logic A output
Safety Output Normal Open
68 SO Logic B output
Safety Output Normal Close
C2000 factory setting Pr. 02-17 (MO2) = 66 (N.O.) and Multi-function Output setting item adds 2
new function: 66 and 68.
Drive status
Safety Output status
N.O.
(MO=66)
N.C.
(MO=68)
Normal run Open Close
STO Close Open
STL1–STL3 Close Open
Content of Multi-function Display
Default: 3
Settings 45: Hardware version

Table of Contents

Other manuals for Delta C2000 Series

Related product manuals