Chapter 11 Summary of Parameter SettingsC2000
11-31
Pr. Parameter Name Setting Range Default
06-05
Acceleration / deceleration time
selection for stall prevention at
constant speed
0: By current acceleration / deceleration time
1: By the 1
st
acceleration / deceleration time
2: By the 2
nd
acceleration / deceleration time
3: By the 3
rd
acceleration / deceleration time
4: By the 4
th
acceleration / deceleration time
5: By automatic acceleration / deceleration
0
06-06
Over-torque detection selection
(OT1)
0: No function
1: Continue operation after over-torque detection
during constant speed operation
2: Stop after over-torque detection during constant
speed operation
3: Continue operation after over-torque detection
during RUN
4: Stop after over-torque detection during RUN
0
06-07 Over-torque detection level (OT1)
10–250% (100% corresponds to the rated current of
the drive)
120
06-08 Over-torque detection time (OT1) 0.0–60.0 sec.
0.1
06-09
Over-torque detection selection
(OT2)
0: No function
1: Continue operation after over-torque detection
during constant speed operation
2: Stop after over-torque detection during constant
speed operation
3: Continue operation after over-torque detection
during RUN
4: Stop after Over-torque detection during RUN
0
06-10 Over-torque detection level (OT2)
10–250% (100% corresponds to the rated current of
the drive)
120
06-11 Over-torque detection time (OT2) 0.0–60.0 sec.
0.1
06-12 Current limit
0–250% (100% corresponds to the rated current of
the drive)
170
06-13
Electronic thermal relay selection
1 (Motor 1)
0: Inverter motor (with external forced cooling)
1: Standard motor (motor with fan on the shaft)
2: Disable
2
06-14
Electronic thermal relay action
time 1 (Motor 1)
30.0–600.0 sec.
60.0
06-15
Temperature level over-heat (OH)
warning
0.0–110.0°C
105.0
06-16
Stall prevention limit level
(Weak magnetic area current stall
prevention level)
0–100% (Pr. 06-03, Pr. 06-04) 100