Chapter 11 Summary of Parameter SettingsC2000
11-34
Pr. Parameter Name Setting Range Default
104: CANopen hardware disconnect (CbFE)
105: CANopen index setting error (CIdE)
106: CANopen slave station number setting error
(CAdE)
107: CANopen index setting exceed limit (CFrE)
111: ictE Internal communication overtime error
(InrCOM)
112: PM sensorless shaft lock error
142: Auto-tuning error 1 (no feedback current error)
(AUE1)
143: Auto-tuning error 2 (motor phase loss error)
(AUE2)
144: Auto-tuning error 3 (no-load current I
0
measuring
error) (AUE3)
148: Auto-tuning error 4 (leakage inductance Lsigma
measuring error) (AUE4)
06-23 Fault output option 1 0–65535 (refer to bit table for fault code)
0
06-24 Fault output option 2 0–65535 (refer to bit table for fault code)
0
06-25 Fault output option 3 0–65535 (refer to bit table for fault code)
0
06-26 Fault output option 4 0–65535 (refer to bit table for fault code)
0
06-27
Electronic thermal relay selection
2 (Motor 2)
0: Inverter motor (with external forced cooling)
1: Standard motor (motor with fan on the shaft)
2: Disable
2
06-28
Electronic thermal relay action
time 2 (Motor 2)
30.0–600.0 sec.
60.0
06-29
PTC detection selection / PT100
motion
0: Warn and continue operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
0
06-30 PTC level / KTY84 Level 0.0–100.0%
50.0
06-31
Frequency command at
malfunction
0.00–599.00Hz
Read
only
06-32 Output frequency at malfunction 0.00–599.00Hz
Read
only
06-33 Output voltage at malfunction 0.0–6553.5V
Read
only
06-34 DC voltage at malfunction 0.0–6553.5V
Read
only
06-35 Output current at malfunction 0.0–6553.5Amp
Read
only

Table of Contents

Other manuals for Delta C2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Series and is the answer not in the manual?

Delta C2000 Series Specifications

General IconGeneral
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Overload Capacity150% of rated current for 60 seconds
CommunicationDeviceNet
ProtectionOvervoltage, Undervoltage, Overcurrent, Overload, Overheat
Humidity5% to 95% (non-condensing)
CoolingForced air cooling
Control ModeV/F Control, Sensorless Vector Control