Chapter 12 Description of Parameter SettingsC2000
12.1-00-21
6. When Y=2, X=3
ORGP
Speed
Position
7. When Y=2, X=4
Zpulse
Speed
Position
8. When Y=2, X=5
Zpulse
Speed
Position
Homing by Frequency 1
Default: 8.00
Settings 0.00–599.00Hz
Homing by Frequency 2
Default: 2.00
Settings 0.00–599.00Hz
Controlled by multi-function input terminal Pr. 02-01–02-08 (44–47).
44: Reverse direction homing (NL)
45: Forward direction homing (PL)
46: Homing (ORG)
47: Homing function enabled
If the drive is not controlled by CAN or PLC, when setting Pr. 00-10 =1 (Control mode = P2P
position control), set the external input terminal to 47 (homing function enable) for homing.
When Pr. 00-10 is set to 3, after homing is complete, you must set control mode (Pr. 00-10 = 1)
to execute P2P position control.
Display Filter Time (Current)
Default: 0.100
Settings 0.001–65.535 sec.
Minimize the current fluctuation displayed by digital keypad.