EasyManua.ls Logo

Delta C2000 Series - Page 418

Delta C2000 Series
936 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 12 Description of Parameter SettingsC2000
12.1-01-5
Output Frequency Upper Limit
Default: 599.00
Settings 0.00–599.00Hz
Output Frequency Lower Limit
Default: 0.00
Settings 0.00–599.00Hz
Use the upper and lower limit output frequency settings to limit the actual output frequency. If the
frequency setting is higher than the upper limit (Pr. 01-10), the drive uses the upper limit
frequency. If output frequency is lower than lower limit (Pr. 01-11) and frequency setting is higher
than minimum frequency (Pr. 01-07), the drive uses the lower limit frequency. Set the upper limit
frequency > lower limit frequency (Pr.01-10 setting value must be > Pr.01-11 setting value).
The upper output frequency limits the maximum output frequency of the drive. If the frequency
setting is higher than Pr.01-10, the Pr. 01-10 setting limits the output frequency.
When the drive starts the slip compensation function (Pr.07-27) or PID feedback control, the drive
output frequency may exceed frequency command but is still limited by this setting.

Table of Contents

Other manuals for Delta C2000 Series

Related product manuals