Chapter 12 Description of Parameter SettingsC2000
12.1-01-11
Auto-acceleration and Auto-deceleration Setting
Default: 0
Settings 0: Linear acceleration and linear deceleration
1: Auto-acceleration and linear deceleration
2: Linear acceleration and auto-deceleration
3: Auto-acceleration and auto-deceleration
4: Stall prevention by auto-acceleration and auto-deceleration (limited by Pr.
01-12 to Pr. 01-21)
0 (linear acceleration and linear deceleration): the drive accelerates and decelerates according to
the setting for Pr. 01-12–01-19.
1 or 2 (auto/linear acceleration and auto/linear deceleration): the drive reduces the mechanical
vibration and prevents the complicated auto-tuning processes. It does not stall during
acceleration and has no need for a brake resistor. It can also improve operation efficiency and
save energy.
3 (auto-acceleration and deceleration–decelerate by actual load): the drive auto-detects the load
torque and accelerates from the fastest acceleration time and smoothest start current to the
setting frequency. When decelerating, the drive auto-detects the load re-generation and stops the
motor smoothly with the fastest deceleration time.
4 (stall prevention by auto-acceleration and deceleration–refer to acceleration and deceleration
time): if the acceleration and deceleration is within a reasonable range, the drive accelerates and
decelerates according to Pr.01-12–01-19. If the acceleration and deceleration time is too short,
the actual acceleration and deceleration time are greater than the acceleration and deceleration
time settings.

Table of Contents

Other manuals for Delta C2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Series and is the answer not in the manual?

Delta C2000 Series Specifications

General IconGeneral
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Overload Capacity150% of rated current for 60 seconds
CommunicationDeviceNet
ProtectionOvervoltage, Undervoltage, Overcurrent, Overload, Overheat
Humidity5% to 95% (non-condensing)
CoolingForced air cooling
Control ModeV/F Control, Sensorless Vector Control

Related product manuals