Chapter 12 Description of Parameter SettingsC2000
12.1-06-6
Over-torque Detection Level (OT1)
Default: 120
Settings 10–250% (100% corresponds to the rated current of the drive)
Over-torque Detection Level (OT1)
Default: 0.1
Settings 0.0–60.0 sec.
Over-torque Detection Level (OT2)
Default: 120
Settings 10–250% (100% corresponds to the rated current of the drive)
Over-torque Detection Time (OT2)
Default: 0.1
Settings 0.0–60.0 sec.
When the output current exceeds the over-torque detection level (Pr. 06-07 or Pr. 06-10) and
exceeds the over-torque detection time (Pr. 06-08 or Pr. 06-11), the over-torque detection follows
the setting of Pr. 06-06 and Pr. 06-09.
When you set Pr. 06-06 or Pr. 06-09 to 1 or 3, an ot1 / ot2 warning displays while the drive keeps
running. The warning remains on until the output current is smaller than 5% of the over-torque
detection level.
When you set Pr. 06-06 or Pr. 06-09 to 2 or 4, an ot1 / ot2 warning displays and the drive stops
running after over-torque detection. The drive keeps running after you manually reset it.

Table of Contents

Other manuals for Delta C2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Series and is the answer not in the manual?

Delta C2000 Series Specifications

General IconGeneral
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Overload Capacity150% of rated current for 60 seconds
CommunicationDeviceNet
ProtectionOvervoltage, Undervoltage, Overcurrent, Overload, Overheat
Humidity5% to 95% (non-condensing)
CoolingForced air cooling
Control ModeV/F Control, Sensorless Vector Control