Chapter 12 Description of Parameter SettingsC2000
12.1-06-18
Status 3: The drive is in STOP; Pr. 06-48 ≠ 0; Pr. 07-02 ≠ 0
When the drive starts, it executes Pr. 06-48 first, and then executes Pr. 07-02 (DC brake). The DC
brake current level in this state includes two parts: one is 20 times the Pr. 06-47 setting value in Pr.
06-48 setting time; the other is the Pr. 07-01 setting value in Pr. 07-02 setting time. In this period,
if an OPHL happens within the time for Pr. 06-48, the drive executes the Pr. 06-45 setting after the
drive starts counting for half the time of Pr. 06-48.
Status 3-1: Pr. 06-48 0, Pr. 07-02 0 (No OPHL detected before operation)
Status 3-2: Pr. 06-480, Pr. 07-200 (OPHL detected before operation)