Chapter 12 Description of Parameter SettingsC2000
12.1-07-11
Automatic Energy-saving Selection
Default: 0
Settings 0: Disable
1: Enable
When energy-saving is enabled, the motor acceleration operates with full voltage. During
constant speed operation, it automatically calculates the best voltage value according to the load
power. This function is not suitable for fluctuating loads or loads which are nearly full during
operation.
When the output frequency is constant (that is, constant operation), the output voltage decreases
automatically as the load decreases. Therefore, the drive operates with minimum multiplication of
voltage and current (electric power).
FOCPG IM:
Steady-speed: Torque current is lower than rated current for 0.35 times and entry into energy
saving mode after 5 seconds.
Return: Torque current is higher than 0.5 times of rated current.

Table of Contents

Other manuals for Delta C2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Series and is the answer not in the manual?

Delta C2000 Series Specifications

General IconGeneral
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Overload Capacity150% of rated current for 60 seconds
CommunicationDeviceNet
ProtectionOvervoltage, Undervoltage, Overcurrent, Overload, Overheat
Humidity5% to 95% (non-condensing)
CoolingForced air cooling
Control ModeV/F Control, Sensorless Vector Control

Related product manuals