Chapter 12 Description of Parameter SettingsC2000
12.2-00-3
3. Press “RUN” to start auto-tuning of IM magnetic flux curve dynamic test for Pr.05-00 = 1 or 6 (motor is
running). Make sure the motor executes auto-tuning under break-away load condition. Check if there
are motor parameters after auto-tuning.
Pr. 05-06 Stator Resistance (Rs) for Induction Motor 1
Pr. 05-07 Rotor Resistance (Rr) for Induction Motor 1
Pr. 05-08 Magnetizing Inductance (Lm) for Induction Motor 1
Pr. 05-09 Stator Inductance (Lx) for Induction Motor 1
4. Execute estimation of the motor inertia (optional). Press “RUN” to start the estimation after finishing
the settings for the parameters mentioned below.
Pr. 00-10 = 2, torque mode
Pr. 00-13 = 2, TQC sensorless
Pr. 05-00 = 12, FOC sensorless inertia estimation (motor is running)
After inertia estimation is finished, check if the estimated value for Pr. 11-01 is reasonable,
refer to the base value table below. (Unit: kg-cm
2
)
Power Setting Power Setting Power Setting
1HP 2.3 25HP 142.8 175HP 2150.0
2HP 4.3 30HP 176.5 250HP 2800.0
3HP 8.3 40HP 202.5 300HP 3550.0
5HP 14.8 50HP 355.5 375HP 5139.0
7.5HP 26.0 60HP 410.8 425HP 5981.0
10HP 35.8 75HP 494.8 475HP 7053.0
12HP 54.8 100HP 1056.5 600HP 9643.0
15HP 74.3 125HP 1275.3 650HP 10734.0
20HP 95.3 150HP 1900.0 750HP 13000.0
5. Execute IM sensorless FOC mode, set up the following parameters:
Pr. 00-10 = 0, set as speed mode
Pr. 00-11 = 5, set as FOC sensorless mode
Pr. 11-00 bit0 =1, use ASR gain auto-tuning
Press RUN” and start the Test with no-load. Accelerate the motor to the rated speed, and then
decelerate to stop, check if the motor runs smoothly.
If the motor runs smoothly, then the setting for IM Sensorless FOC is completed.
If the motor does not run smoothly, or fails to start at low-frequency, then refer to the
following steps for adjustment.
6. Select auto-tuning gain (Pr. 11-00 bit0=1), adjust ASR parameters according to the speed response.
Pr. 11-00 bit0 =1, use auto-tuning for ASR
Pr. 11-03 ASR1 low-speed bandwidth (When the acceleration of low-speed cannot follow the
acceleration command, increase the low-speed bandwidth)
Pr. 11-04 ASR2 high-speed bandwidth (When the acceleration in high speed causes vibration or
cannot follow the acceleration command, increase high-speed bandwidth)
Pr. 11-05 Zero-speed bandwidth (If the response of start-up is slow or incapable, increase
zero-speed bandwidth)
The bigger the setting value for ASR bandwidth, the faster the response.

Table of Contents

Other manuals for Delta C2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Series and is the answer not in the manual?

Delta C2000 Series Specifications

General IconGeneral
BrandDelta
ModelC2000 Series
CategoryDC Drives
LanguageEnglish

Related product manuals