Chapter 9 Specification
ME300
9-2 230V Models
230V, one-phase
Frame A B A B A B
Model VFD_ _ _ ME21 _ _ _AA
ANN
ANS AFN
AFS ANN
ANS
AFN
AFS ANN
ANS
AFN
AFS
Applicable Motor Output (kW) 0.1 0.2 0.4
Applicable Motor Output (HP) 1/8 1/4 1/2
Heavy
duty
Rated Output Capacity (kVA) 0.3 0.6 1.1
Carrier Frequency (kHz) 2–15
Normal
Duty
Rated Output Capacity (kVA) 0.4 0.7 1.2
Rated Output Current (A) 1.0 1.8 3.2
Carrier Frequency (kHz) 2–15
Rated Input
Current (A)
Heavy Duty 2.2 3.4 5.9
Normal Duty 2.8 3.8 6.7
Rated Voltage / Frequency One-phase AC 200–240 V (-15– +10%), 50/60 Hz
Operating Voltage Range (V
AC
) 170–265
Frequency Range (Hz) 47–63
Weight (kg) 0.4 0.9 0.4 0.9 0.5 0.9
Cooling Method Convective cooling Fan cooling
Ingress Protection Rating IP20
Frame B C
Model VFD_ _ _ ME21 _ _ _AA
4A8 7A5 11A
ANN
ANS AFN
AFS ANN
ANS AFN
AFS ANN
ANS AFN
AFS
Applicable Motor Output (kW) 0.75 1.5 2.2
Applicable Motor Output (HP)
Heavy
duty
Rated Output Capacity (kVA) 1.8 2.9 4.2
Rated Output Current (A) 4.8 7.5 11
Normal
Duty
Rated Output Capacity (kVA) 1.9 3.2 4.8
Rated Output Current (A) 5 8.5 12.5
Rated Input
Current (A)
Heavy Duty 10.1 15.8 23.1
Normal Duty 10.5 17.9 26.3
Rated Voltage / Frequency One-phase AC 200–240 V (-15– +10%), 50/60 Hz
Operating Voltage Range (V
AC
) 170–265
Weight (kg) 0.8 0.9 1 1.5 1 1.5
Cooling Method Convective cooling Fan cooling
EMC Filter Optional Built-in Optional Built-in Optional Built-in
Ingress Protection Rating IP20
Table 9-2
NOTE:
1. Default: heavy duty.
2. The value of the carrier frequency is set in the factory. To increase the carrier frequency, decrease the current. See the derating
curve diagram in Section 9-6 for more information.
3. When the load is a shock or impact load, use a higher level model.