Chapter 9 Specification
ME300
230V, three-phase
Frame A
Model VFD_ _ _ ME23_ _ _AA
ANN
ANS ANN
ANS ANN
ANS ANN
ANS
Applicable Motor Output (kW) 0.1 0.2 0.4 0.75
Applicable Motor Output (HP) 1/8 1/4 1/2 1
Heavy
duty
Rated Output Capacity (kVA) 0.3 0.6 1.1 1.8
Carrier Frequency (kHz) 2–15
Duty
Rated Output Capacity (kVA) 0.4 0.7 1.2 1.9
Rated Output Current (A) 1.0 1.8 3.2 5
Carrier Frequency (kHz) 2–15
Rated Input
Current (A)
Heavy Duty 2.2 1.9 3.4 5.8
Normal Duty 2.8 2.2 3.8 6.0
Rated Voltage / Frequency Three-phase AC 200–240 V (-15– +10%), 50/60 Hz
Operating Voltage Range (V
AC
) 170–265
Frequency Range (Hz) 47–63
Weight (kg) 0.4 0.4 0.45 0.6
Cooling Method Convective cooling
Ingress Protection Rating IP20
Frame B C D
Model VFD_ _ _ ME23_ _ _AA
7A5 11A 17A 25A
ANN
ANS ANN
ANS ANN
ANS ANN
ANS
Applicable Motor Output (kW) 1.5 2.2 3.7 / 4 5.5
Applicable Motor Output (HP)
Rating
Heavy
duty
Rated Output Capacity (kVA) 2.9 4.2 6.5 9.5
Rated Output Current (A) 7.5 11 17 25
Duty
Rated Output Capacity (kVA) 3.0 4.8 7.4 10.3
Rated Output Current (A) 8.0 12.5 19.5 27
Rated Input
Current (A)
Heavy Duty 9.0 13.2 20.4 30
Normal Duty 9.6 15 23.4 32.4
Rated Voltage / Frequency Three-phase AC 200–240 V (-15– +10%), 50/60 Hz
Operating Voltage Range (V
AC
) 170–265
Weight (kg) 0.8 1 1 2
Cooling Method Fan cooling
EMC Filter Optional
Ingress Protection Rating IP20
Table 9-3
NOTE:
1. Default: heavy duty.
2. The value of the carrier frequency is set in the factory. To increase the carrier frequency, decrease the current. See the derating
curve diagram in Section 9-6 for more information.
3. When the load is a shock or impact load, use a higher level model.