Chapter 11 Summary of Parameter SettingsME300
11-4
Pr. Explanation Settings Default
19: The corresponding CPU digital input pin status (d)
20: The corresponding CPU digital output pin status (0.)
25: Overload count (0.00–100.00%) (o.) (unit: %)
26: Ground fault GFF (G.) (unit: %)
27: DC bus voltage ripple (r.) (unit:
V
DC
)
30: Display the output of User-defined (U)
31: Display Pr.00-05 user gain (K)
35: Control mode display:
0 = Speed control mode (SPD)
36: Present operating carrier frequency of the drive (J.)
(Unit: Hz)
38: Display the drive status (6.)
41: kWh display (J) (unit: kWh)
42: PID target value (h.) (unit: %)
43: PID compensation (o.) (unit: %)
44: PID output frequency (b.) (unit: Hz)
47: Master frequency value (A) (unit: Hz)
60: Display PID setting and feedback signal
61: Display the content of the running program ( 1=tt )
00-05
Coefficient gain in actual
output frequency
0.00–160.00 1.00
00-06 Firmware version Read only Read only
00-07
Parameter protection
password input
0–65535
0–4: the number of password attempts allowed
0
00-08
Parameter protection
password setting
0–65535
0: No password protection or password entered
incorrectly (Pr.00-07)
1: Password has been set
0
00-10 Control mode 0: Speed mode 0
00-11 Speed Control mode
0: IM VF (IM V/F control)
2: IM / PM SVC (IM / PM space vector control)
0
00-16 Load selection
0: Normal load
1: Heavy load
1
00-17 Carrier frequency
Normal load: 2–15 kHz
Heavy load: 2–15 kHz
4
4
00-20
Master frequency
command source
(AUTO, REMOTE)
0: Digital keypad
1: RS-485 communication input
2: External analog input (refer to Pr.03-00)
3: External UP / DOWN terminal
(multi-function input terminals)
0