Chapter 12 Description of Parameter Settings
ME300
point), and the corresponding unit to the third decimal place is 0003h, then inWG and the third
decimal point displayed in hexadecimal is 01A3h, that is 419 in decimal value. Thus, set Pr.00-25
= 419 to complete the setting.
Maximum User-Defined Value
Default: 0
Settings
0: Disable
0–65535 (when Pr.00-25 set to no decimal place)
0.0–6553.5 (when Pr.00-25 set to one decimal place)
0.00–655.35 (when Pr.00-25 set to two decimal places)
0.000–65.535 (when Pr.00-25 set to three decimal places)
When Pr.00-26 is NOT set to 0, the user-defined value is enabled. After selecting the displayed
unit and number of decimal points with Pr.00-25, the setting value of Pr.00-26 corresponds to
Pr.01-00 (Maximum motor operating frequency), and then the motor operation frequency has a
linear relationship with the displayed value on the digital keypad.
Example:
When the frequency set in Pr.01-00 = 60.00 Hz, the maximum user-defined value for Pr.00-26 is
100.0%. This also means that Pr.00-25 is set at 33 (0021h) to select % as the unit.
NOTE:
Set Pr.00-25 before using Pr.00-26. After you finish setting, when Pr.00-26 is not 0, the displayed
unit on the keypad shows correctly according to Pr.00-25 settings.
Default: Read only
Settings
Read only
Pr.00-27 displays the user-defined value when Pr.00-26 is not set to 0.
The user-defined value is valid only when Pr.00-20 (frequency source) is set to the digital keypad
or to RS-485 communication.
Default: 0
Settings 0: Standard HOA function
1: Switch Local / Remote, the drive stops
2: Switch Local / Remote, the drive runs as the REMOTE setting for
frequency and operation status
3: Switch Local / Remote, the drive runs as the LOCAL setting for frequency
and operation status
4: Switch Local / Remote, the drive runs as LOCAL setting when switched to
Local and runs as REMOTE setting when switched to Remote for frequency
and operating status.
The default for Pr.00-29 is 0, that is, the standard HOA (Hand-Off-Auto) function. Set the AUTO
and HAND frequency and operation source with Pr.00-20, 00-21 and Pr.00-30, 00-31. The
external terminal function (MI) = 56 for LOC / REM mode selection is disabled when Pr.00-29=0.