Chapter 12 Description of Parameter Settings
ME300
12.1-13-1
13 Industry Application Parameters
13-00
Application Selection
D
efault: 00
S
ettings 00: Disabled
01: User-Defined parameter
03: Fan
04: Pump
05: Conveyor
07: Packing
10: Logistics
11: Tension PID
12: Tension PID + master / auxiliary frequency
Note: after you select the macro, some of the default values adjust automatically according to the
application selection.
Group setting 03: Fan
The following table lists the relevant fan setting application parameters.
Pr. Explanation Settings
00-11 Speed control mode 0 (IM V/F)
00-16 Load selection 0 (Normal load)
00-17 Carrier frequency Default setting
00-20
Master frequency command source
(AUTO, REMOTE)
2 (External analog input)
00-21 Operation command source (AUTO, REMOTE) 1 (External terminals)
00-22 Stop method 1 (Coast to stop)
00-23 Motor direction control 1 (Disable reverse)
00-30
Master frequency command source
(HAND, LOCAL)
0 (Digital keypad)
00-31 Operation command source (HAND, LOCAL) 0 (Digital keypad)
01-00 Motor 1 maximum operation frequency Default setting
01-01 Motor 1 output frequency Default setting
01-02 Motor 1 output voltage Default setting
01-03 Motor 1 mid-point frequency 1 Default setting
01-04 Motor 1 mid-point voltage 1 Default setting
01-05 Motor 1 mid-point frequency 2 Default setting
01-06 Motor 1 mid-point voltage 2 Default setting
01-07 Motor 1 minimum output frequency Default setting
01-08 Motor 1 minimum output voltage Default setting
01-10 Output frequency upper limit 50.00 (Hz)
01-11 Output frequency lower limit 35.00 (Hz)
01-12 Acceleration time 1 15.00 (sec.)