EasyManua.ls Logo

Delta MS300 - Page 50

Delta MS300
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MS300/MH300 PROFINET Communication Card CMM-PN02
CMM-PN02 Operation Manual
50
3. The figure below shows that you read Pr.01-00, Pr.01-10 and Pr.09-00 and write Pr.01-00 and
Pr.09-00.
Thus, to synchronously read or write the drive parameters through the PLC program, simply add
40 bytes to the start address of the I/O address. The added value is the home position of the
parameter table. Take the figure above as an example, to read the values from Pr.01-00 in the
PLC program, read %IW296:P. Similarly, to write the values in Pr.01-00 in the PLC program,
write %QW296:P.
If you do not know the start address of the I/O address, refer to the figure below and follow the
four steps to open the I/O Address.

Other manuals for Delta MS300

Related product manuals