EasyManua.ls Logo

Delta MS300 - Page 51

Delta MS300
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MS300/MH300 PROFINET Communication Card CMM-PN02
CMM-PN02 Operation Manual
51
4. After you finish setting up the parameter table, recompile the programs and download them to
the PLC program, and then reboot the drive to make CMM-PN02 receive the updated
parameter settings.
5. When CMM-PN02 is connected to the PLC program successfully, you can test the reading or
writing of the set parameter by using the Watch Table. Refer to the figure below for The Watch
Table.
Follow the four steps below to verify if the settings for the parameter table are applicable and
if reading or writing the drive parameters is successful (Use the keypad to verify.).
NOTE 1: The figure above shows that %IW312 is the status value returned when the parameter table reads or
writes the parameters. Low byte is the status value of reading, whereas high byte is the status value of
writing. Take the figure above as an example, if the status value is 0x8183, the values of 1, 2, and 8 in the
parameter table are successfully read and the values of 1 and 8 are successfully written. Thus, the
success or failure of the parameter reading/writing depends on this status value.
NOTE 2: %IW312 = I/O start address + 56 (the I/O start address in this example is 256).
NOTE 3: Depending on the immediacy of the data, you can choose to write the parameters periodically or
non-periodically
,

Other manuals for Delta MS300

Related product manuals