EasyManuals Logo
Home>Delta>Inverter>RPI M6A

Delta RPI M6A User Manual

Delta RPI M6A
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
57
Installation and Operation Manual for RPI M6A M8A M10A inverters V1.0 2016-02-03
6 Installation
6.7 Grounding the inverter housing
Typically yellow/green copper cable with minimum wire size
6 mm
2
has to be used.
Always consider local regulation regarding the cable require-
ments.
In the absence of such regulations, it is nonetheless recom-
mended to ground the inverter housing for safety reasons before
setting up the electrical connections. External grounding is rec-
ommended in addition to PE connection within the AC connec-
tion.
1. On the left side, ground the inverter housing. The ground-
ing screw is delivered with the inverter and mounted to the
inverter.
Toothed lock ring
Grounding cable
Washer
Spring washer
M6 screw
Perform a continuity check for the grounding con-
nection. If the test fails, scratch the paint off the
inverter housing below the tooth lock washer to get
a better electrical connection.

Table of Contents

Other manuals for Delta RPI M6A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta RPI M6A and is the answer not in the manual?

Delta RPI M6A Specifications

General IconGeneral
BrandDelta
ModelRPI M6A
CategoryInverter
LanguageEnglish

Related product manuals