Installation and Operation Manual for RPI M6A M8A M10A inverters V1.0 2016-02-03
8 Settings
Congurable Parameters
Parameter Description Value range
High Off
Frequency High Off
45.00 ... 65.00 Hz
High On
Frequency High On
45.00 ... 65.00 Hz
High Off T
Disconnection time for Frequency High Off
0.0 ... 5.0 s
Low Off
Frequency Low Off
45.00 ... 65.00 Hz
Low On
Frequency Low On
45.00 ... 65.00 Hz
Low Off T
Disconnection time for Frequency Low Off
0.0 ... 5.0 s
Hi Off Slow
Frequency High Off Slow
45.00 ... 65.00 Hz
Hi On Slow
Frequency High On Slow
45.00 ... 65.00 Hz
Hi Off Sl T
Disconnection time for Frequency High Off Slow
0.0 ... 600.0 s
Lo Off Slow
Frequency Low Off Slow
45.00 ... 65.00 Hz
Lo On Slow
Frequency Low On Slow
45.00 ... 65.00 Hz
Lo Off Sl T
Disconnection time for Frequency Low Off Slow
0.0 ... 600.0 s
Do not change this setting without prior
consultation with Delta Solar Support.