8 Settings
Installation and Operation Manual for RPI M6A M8A M10A inverters V1.0 2016-02-03
98
Congurable Parameters
Parameter Description Value range
Mode
OFF Switches the function on and off.
Curve A
Curve B
OFF | Curve A | Curve B
Default value: OFF
V1s
The lower voltage limit for feeding-in capacitive reactive power.
230.0 ... 264.5 V
V2s
The upper voltage limit for feeding-in capacitive reactive power.
230.0 ... 264.5 V
Qs limit
The limit for the inductive apparent power. The value is set in per cent
of the rated apparent power S
n
. This value is connected with param-
eter V2s.
0 ... cap 63%
V1i
The upper voltage limit for feeding-in inductive reactive power.
184.0 ... 230.0 V
V2i
The upper voltage limit for feeding-in inductive reactive power.
84.0 ... 230.0 V
Qi limit
The limit for the inductive apparent power. The value is set in per cent
of the rated apparent power S
n
. This value is connected with param-
eter V2i.
0 ... ind 63%
T delay
Internal parameter
0 ... 120.00 s
P lock-in
The lower limit of the active power range within which the function is
active. The parameter is given in percent of the nominal power. Used
for Italy only.
10 ... 100%
P lock-out
The upper limit of the active power range within which the function is
active. The parameter is given in percent of the nominal power. Used
for Italy only.
5 ... 10%
Do not change this setting without prior
consultation with Delta Solar Support.