114
Technical data
12. Technical data
12.1 
NOTE
The specication is subject to change. Please check the web site at
www.solar-inverter.com for the latest version.
10EUT4TL 15EUG4TL 20EUG4TL 30EUT4TL
INPUT (DC)
Max. recommended
PV power
1)
13.2 kW
P
19 kW
P
25 kW
P
38 kW
P
Recommended PV
power range
8.8 ... 13.2 kW
P
14 ... 19 kW
P
18 ... 25 kW
P
26 ... 38 kW
P
Nominal power 10.5 kW 15.3 kW 20.4 kW 31 kW
Operating voltage 250 ... 1000 V
MPP voltage range @
nominal power,
balanced inputs
350 ... 850 V
DC
350 ... 800
V
DC
350 ... 800 V
DC
480 ... 800 V
DC
MPP voltage range
unbalanced inputs
350 ... 850 V
DC
470 ... 800 V
DC
480 ... 800 V
DC
620 ... 800 V
DC
Nominal voltage 635 V
DC
650 V
DC
Start up power 40 W
Absolute maximum
voltage
1000 V 1000 V 1000 V
Number of inputs 4 inputs (2 MPP trackers) 6 inputs (2 MPP
trackers)
Max. current 30 A (20 A x 2) 48 A (24 A x 2) 60 A (30 A x 2) 68 A (34 A x 2)
OUTPUT (AC)
Max. apparent power
2)
10.5 kVA 15.75 kVA 21.0 kVA 31.5 kVA
Nominal apparent
power
10.0 kVA 15.0 kVA 20.0 kVA 30.0 kVA
Voltage range
(3 phase)
3)
3 x 230 / 400 V (± 20 %) + N + PE (3 phases, 5 wires)
Nominal current 14.5 A 22 A 29 A 43 A
Max. current 16 A 25 A 32 A 46 A
Nominal frequency 50/60 Hz
Frequency range
3)
50 / 60 Hz ± 5 Hz
Power factor adjust-
able
0.80 Cap ... 0.80 Ind

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta SOLIVIA 10 EU T4 TL and is the answer not in the manual?

Delta SOLIVIA 10 EU T4 TL Specifications

General IconGeneral
BrandDelta
ModelSOLIVIA 10 EU T4 TL
CategoryInverter
LanguageEnglish

Related product manuals