57
EN
Wiring the Inverter
Input Current 1
Input Current 2
Input Current [A]Input Current [A]
Input Voltage [V]
Input Voltage [V]
Balanced Input Power
Unbalanced Input Power 33/67
Input Current 1
Input Current 2
Max. Power MPPT Range
Max. Power MPPT Range
Max. Current
Max. Current
Figure 6.10.: Comparison diagram of Balanced Power Input and Unbalanced Power Input
Maximum rating of input power:
Model Max. Input Current Max. Power MPPT
Range balanced
(50/50)
Max. Power MPPT
Range unbalanced
(33/67)
SOLIVIA 10 TL 20 A x 2 350 - 850 Vdc 350 - 850 Vdc*
SOLIVIA 15 TL 24 A x 2 350 - 800 Vdc 470 - 800 Vdc
SOLIVIA 20 TL 30 A x 2 350 - 800 Vdc 480 - 800 Vdc
SOLIVIA 30 TL 34 A x 2 480 - 800 Vdc 620 - 800 Vdc
*Note: Unlike the 15 / 20 / 30 TL, the 10 TL has a xed max. power MPPT voltage range. For
unbalanced loads, the 10 TL will adjust the input current to provide an optimum adjustment.