www.opwglobal.com
Combo Dual Level/ Hydrocarbon Liquid Sump
Sensor
Part #30-3225
This sensor is made from the Hydrocarbon Liquid Sump Sensor (30-
3219-12) with a Dual-Level Reservoir Sensor (30-3221-2) clipped to
its side. The combination sensor is designed to detect the presence of
liquid hydrocarbons and water in sumps, dispenser pans and other
locations where the presence of a liquid could indicate that a leak has
occurred.
The sensor contains a carbon/polymer material that changes
resistance when exposed to liquid hydrocarbons. The level sensor
portion simply clips onto the hydrocarbon sensor and can be
positioned at any desired height to activate in the presence of liquid.
Combo Dual Level / Hydrocarbon Liquid Sump Sensor
Combo Dual Level/Hydrocarbon Liquid Sump Sensor
Substances Detected:
Liquid Hydrocarbon and Water
Operating Temperature:
-4°F to 122°F (-20°C to +50°C)
Dimensions:
30-3221-2
30-3219-12
2.4” x 14” (6 cm x 35.6 cm)
1.7” x 13.2” (4.4 cm x 33.5 cm)
Required Cable:
12’ (3.6 m) of gas-and-oil resistant cable
Maximum Wiring Length*:
1,000’ (305 m)
Nominal resistance
(uncontaminated):
1K - 5K ohms
Nominal resistance
(contaminated):
30K - 200K ohms
Multi-Drop Restriction:
1 per channel
Connections:
Channel 1: Red = Power, White = Signal
Channel 2: Black = Signal
*Maximum Wiring Length is the maximum length of cable to be used
to connect all sensors on an individual channel. The length includes
run of cable from VSmart to each sensor board in the string.