Interstitial Optical Liquid Sensor
Part #30-3223
The Interstitial Optical Liquid Sensor is used primarily to monitor the
interstitial area of double-walled tanks. This sensor incorporates a
long-life optical prism and can also be used in sumps, dispenser pans
and other locations where the presence of a liquid could indicate that a
leak has occurred.
The sensor does not differentiate between water and hydrocarbon
liquid. In the event of a break in the cable, the system will activate the
alarm.
Interstitial Optical Liquid Sensor
Interstitial Optical Liquid Sensor
Substance Detected:
Liquid
Operating Temperature:
-4°F to 122°F (-20°C to +50°C)
Dimensions:
0.7” x 2.8” (1.8 cm x 7 cm)
Required Cable:
20’ (6 m) gas-and-oil resistant cable
Maximum Wiring Length*:
1,000’ (305 m)
Multi-Drop Restriction:
1 per channel
Connections:
Red = Power, White = Signal, Black =
Ground
*Maximum Wiring Length is the maximum length of cable to be used
to connect all sensors on an individual channel. The length includes
run of cable from VSmart to each sensor board in the string.