EasyManua.ls Logo

Dover OPW SiteSentinel iSite - 5.3 Interstitial Level Sensor Float Switch

Dover OPW SiteSentinel iSite
146 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 42 of 145
www.opwglobal.com
5.3
Interstitial Level Sensor Float Switch
Part No. 30-0231-S
Interstitial Level Sensors (Figure 5-3) are used primarily in the interstitial
area of a steel double-walled tank. The sensor contains a float switch
that activates in the presence of a liquid. The sensor is constructed from
chemical-resistant non-metallic material. It can also be used in sumps,
dispenser pans and other locations where the presence of a liquid could
indicate that a leak has occurred. In the event of a break in the cable,
the system will activate the alarm.
This technology allows the SiteSentineiSite™ and VSmart Module to
automatically detect sensor connection, sensor type and sensor status,
will minimize user entry error and identify hardware issues with minimal
troubleshooting.
IntelliSense
Board
Figure 5-3 Interstitial Level Sensor Float Switch
Interstitial Level Sensor Float Switch Specifications
Primary Use(s):
Interstitial Area
Alternate Use(s):
Sumps and Dispenser Pans
Detects:
Liquid
Operating Temperature:
40°F to +168°F (40°C to +70°C)
Dimensions:
Length: 3.9” (9.9 cm), Diameter: 1.3” (3.3 cm)
Cable Requirements:
Belden #88760 or Alpha #55371
Maximum Wiring Length*:
1,000’ (305 m) field wiring
Multi-Drop Restriction:
16 per I.S. barrier channel (64 per barrier)
Connections:
Red = Power, Black = Signal, Shield = Ground