Deactivating transmitters
This function is used to disable a transmitter.
When a transmitter is disabled, all the alarms and faults are suppressed. In
measurement mode the measured value for that transmitter is replaced by the
word » disabled « in the display, e.g.
In measurement mode:
Press [ u ] key.
Enter password (for maintenance or configuration).
Press [ u ] key to change over to menu mode.
Display:
Use [ q ] or [ l ] key to select the » TRANSMITTER ACTIVE « option.
Press [ u ] key –
The display shows whether the transmitter with the lowest bus address is
active, e.g.:
Use the [ q ] or [ l ] key to call up all the other transmitters.
Use the [ k ] or [ j ] key to enable/disable the selected transmitter:
» j « (yes) = transmitter enabled,
» n « (no) = transmitter disabled.
To quit the function:
Press [ u ] key to quit the function and display the menu option again.
75
Menu mode
Deactivating transmitters
MENU:
MEASUREMENT
MENU:
TRANSMITTER ACTIVE
Transmitter 0
enabled y / n
MENU:
TRANSMITTER ACTIVE
Transmitter 5
enabled y / n
Transmitter 5
disabled

Other manuals for Dräger VarioGard

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dräger VarioGard and is the answer not in the manual?

Dräger VarioGard Specifications

General IconGeneral
BrandDräger
ModelVarioGard
CategoryControl Unit
LanguageEnglish

Related product manuals