EasyManua.ls Logo

Dräger VarioGard - Electrical Installation

Dräger VarioGard
46 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical installation
The VarioGard system wiring may only be routed and connected by an
electrician in accordance with the relevant regulations.
Shielded cables are not required.
Only a limited number of system components such as transmitters can be
connected to a single central unit.
The various system components place different loads on the central unit.
The load is indicated in ”busloads”.
The individual system components (slaves) represent the following loads:
The total of all the busloads must not exceed 16 without an additional power
supply. The maximum total cable lengths, depending on the total planned
busloads, are shown below:
Larger systems with cable lengths up to 1170 m or 24 busloads are also
possible, depending on the conditions prevailing in the individual systems.
Dräger Safety AG & Co. KGaA must be consulted with regard to the
technical details in such cases.
Installing the VarioGard system
Electrical installation
50
Slave Busloads
Transmitter with electrochemical Dräger
sensor
1
Relay module 2
Converter modulel
for each 4 … 20 mA loop connected which
is supplied by the VarioGard system bus
(i.e. maximum of 1 + 4 x 0.75 = 4 busloads)
1
0.75
Cross-section 2 4 6 8 10 12 14 16
JE-Y(St)Y 2 x 2 x 0,8 mm (0,5 mm
2
) 900 m 810 m 540 m 400 m 320 m 270 m 230 m 200 m
H05VV-R3 X 1,5 (NYM-O) 1.5 mm
2
1170 m 1170 m 1170 m 1170 m 1000 m 820 m 700 m 610 m
Number of busloads

Other manuals for Dräger VarioGard

Related product manuals