[381] Second Communicator Options
[382] Third Communicator Options
Option Description
[1]
Ringback
ON: Opening After Alarm Keypad Ringback Enabled. When the Opening After Alarm reporting code is successfully
transmitted to the monitoring station, the keypad sounds a series of 8 beeps to confirm to the end user that the Opening After
Alarm Code was sent and received. This Ringback occurs for each Opening After Alarm code successfully reported.
OFF: Opening After Alarm Ringback Disabled. When the opening after alarm reporting code is successfully trans-
mitted to the monitoring station, no keypad indications will be provided.
[2]
Future Use
[3]
SIA
Reporting
Codes
ON: SIA Uses Programmed Reporting Codes. This option is for use with the SIA communication format. If 00 is
programmed in the reporting code section, the event will not be communicated. When this option is ON and there is a
valid reporting code programmed in the reporting code section, the programmed reporting code will be transmitted. If
FF is programmed as a reporting code, the event will not be communicated.
Reporting Code Entry Option ON Option OFF
00 No Transmission No Transmission
FF No Transmission Auto Rep Code Sent
01-FE 01-FE Sent Auto Rep Code Sent
OFF: SIA Uses Automatic Reporting Codes. When this option is OFF and there is a valid reporting code (01-FE) or
FF programmed in the reporting code section, the panel transmits an automatic reporting code for SIA only. This
would be used when automatic reporting codes are required but there is a requirement for a different reporting code
(like a pulse format).
[4]
Closing
Confirmation
ON: Closing Confirmation Enabled. The system beeps the keypad 8 times after successfully transmitting a Closing
reporting event.
OFF: Closing Confirmation Disabled. The keypad does not beep.
[5]-[6]
Future Use
[7]
CID
Reporting
Codes
ON: Contact ID Uses Programmed Reporting Codes. The Contact ID communications format uses programmed
reporting codes when transmitting to a central station.
OFF: Contact ID Uses Automatic Reporting Codes. The Contact ID communications format uses automatic report-
ing codes as shown in Appendix A when transmitting to central station.
[8] Future Use
Option Description
[1] Future Use
[2]
Walk Test
Communications
ON: Alarm Communications Enabled During Walk Test. The system transmits all alarms during Walk Test.
OFF: Alarm Communications Disabled During Walk Test. The system does not report alarm events during
Walk Test, even if alarms are programmed.
[3]
Communications
Cancelled Message
ON: Communications Cancelled Message Enabled. The Communications Cancelled (LCD) or CC (Icon) mes-
sage will be displayed if alarms are acknowledged during the transmission delay time + arming cancellation win-
dow. This message will be displayed for 5 seconds on all keypads. The acknowledgement can be made with an
access code, disarming function key or a Keyswitch zone.
OFF: Communications Cancelled Message Disabled. The Communications Cancelled LCD message and CC
Icon keypad message will not be created by any method.
[4]
Call Waiting
Cancel
ON: Call Waiting Cancel Enabled. The call waiting dialing string programmed in Section [304] will be dialed
before the first attempt of each phone number. All subsequent dialing attempts to the same phone number will not
use the call waiting cancel string.
OFF: Call Waiting Cancel Disabled. The system does not dial the Call Waiting Cancel string.
Note: A call waiting cancel on a non-call waiting line will prevent successful connection to the central station.
[5]
Future Use
[6]
AC Fail
Communications
Timing
ON: System AC Failure Transmission Delay in Hours. The System AC Failure Transmission Delay in Section
[377], Option 5 is programmed in hours.
OFF: System AC Failure Transmission Delay in Minutes. The System AC Failure Transmission Delay in Sec-
tion [377], Option 5 is programmed in minutes.