Installer Code Access
Master Code Access
Turn internal piezo siren (and external siren, if connected) on or off.
UL Note: for UL/cUL the Siren is not allowed to be turned off to not
operate. This will not disable panics.
Panel siren pauses periodically to announce which locations have
triggered the alarm. UL Note: for UL/cUL this feature is not allowed
for Fire, CO, Burglar Alarm.
When disabled, fire alarm is triggered with a single fire event from
smoke detector. When enabled, panel requires two fire events from
smoke detector (one detector twice or two detects once each)
Severe Weather Siren
Warning
When enabled, siren will sound when the panel receives a severe
weather alert. When disabled, panel will use severe weather chime.
UL NOTE: this functionality has not been evaluated by UL/cUL..
Amount of time (in seconds) before panel will attempt call to
central station after an alarm event is triggered!
When SIA Limits enabled: :15 to :45 seconds!
When SIA Limits disabled: :05 to :254 seconds.
Note: maximum delay for UL/cUL shall be set for 30 sec.
Determine how long before siren stops sounding during an alarm
event (4 minutes to 8 minutes). For UL/cUL the minimum bell time
out shall be set to 5min.
When enabled, siren will sound when a water or freeze detector is
triggered. When disabled, the panel emits a “water” tone.
Allow Master Code To
Access Siren and Alarms
Allow the master code to access these features and settings. !
Note: not allowed for UL/cUL.