DYNISCO UPR800 Series Instruction Manual
Page | 73
Default value: Failsafe mode
ALARM 2 HYSTERESIS - Group 4
Available: Only if A2.LNK is different than OFF
Upper display: Alarm 2 hysteresis
Lower display: A2.HYS
Range: From 0.1 to 10.0% of the selected range
Default value: 1.0%
ALARM 2 RESET MODE - Group 4
Available: Only if A2.LNK is different than OFF
Upper display: Selected reset mode for alarm 2
Lower display: A2.RES
Range: Auto, LAtCh. Automatic reset, manual reset
Default value: Auto
ALARM 2 FAILSAFE MODE - Group 4
Available: Only if A2.LNK is different than OFF
Upper display: Selected failsafe mode for alarm 1
Lower display: A2.FSM
Range: FS, nFS. Failsafe mode, non-failsafe mode
Default value: Failsafe mode
ALARM 3 HYSTERESIS - Group 4
Available: Only if A3.LNK is different than OFF
Upper display: Alarm 3 hysteresis
Lower display: A3.HYS
Range: From 0.1 to 10.0% of the selected range
Default value: 1.0%
ALARM 3 RESET MODE - Group 4
Available: Only if A3.LNK is different than OFF
Upper display: Selected reset mode for alarm 3
Lower display: A3.RES
Range: Auto, LAtCh. Automatic reset, manual reset
Default value: Auto
ALARM 3 FAILSAFE MODE - Group 4
Available: Only if A3.LNK is different than OFF
Upper display: Selected failsafe mode for alarm 1
Lower display: A3.FSM
Range: FS, nFS. Failsafe mode, non-failsafe mode
Default value: Failsafe mode
LOGIC INPUT CONFIGURATION - Group 4
Available: Always
Upper display: Configuration of logic input